Lennox C0SNSR30AE, Return Air Duct Relative Humidity Sensor, Non-Communicating, 24 VAC
Cat # : 76M31
Model/Part # : C0SNSR30AE
Quantity:
Product Overview
Lennox C0SNSR30AE, Return Air Duct Relative Humidity Sensor, Non-Communicating, 24 VAC
Non-communicating return air duct mounted RH sensor designed for applications that require mounting the sensor in the return air duct. Sensor may be used for Humiditrol® units or units that use the IMC Supermarket reheat feature.
- Terminal blocks for wiring connections.
- Relative humidity range: 0 -100%.
- Controller Compatibility: IMC, Building Controller, Network Thermostat Controller
- Operating Environment Temperature: –10°F to 160°F
- Humidity: 0-95% RH, non-condensing
- Power Requirements: 24VAC (+/–25%), 50/60Hz, 1.5 VA
- RH Range: 5-95%
- Accuracy: +/-3% RH from 20 to 95% RH @77°F
- Enclosure: High impact ABS off-white plastic case
- Dimensions: Electronics Enclosure: 4 in. dia x 2-1/4 in.
- Duct Probe: 7-7/8 in. x 3/4 in. diameter
- Analog Output 0-10VDC, 0-5VDC or 4-20mA (0-10VDC is used for IMC, Building Controller and Network Thermostat Controller)